Risk area 2 – ISO 8

  • High moderate risk of infection
    – Specific class of air: ISO 8 (less than 3,520,000 particles of 0.5 micron per m³ of air)
    – Particulate elimination class at 0.5 micron: CP20
    – Microbiological cleanliness class: M100
  • Air handling equipment
    – STERIBLOC type cabinet – Filtration F6 + F7 + H13 (conforms to standard EN 1886)
    – Distribution of treated air ensured by diffusers or induction grilles
    – No final filtration in the treated area
    – Room renewal rate greater than or equal to 10 vol / h
    – Fresh air rate in room 6 vol / h
    – Room overpressure: 15 Pa (fresh air / return air differential)
    – Air temperature (except specific needs): 19 ° C to 26 ° C
    – Air humidity: 45% to 65% RH
    – Maximum acoustic pressure in the room and in activity: 40 to 48 dBA