PSOP

PSOP

The low speed filtering ceiling

Aseptic and hyper aseptic operating theatres

The low-speed filtering ceiling is designated for aseptic and hyper aseptic operating theatres

Its structure equipped with H14 absolute filters guarantees a uniform air flow over the risk area.

The structure includes a supply plenum equipped with absolute filters of H14 efficiency (standard size).

This plenum forms a pressure chamber upstream of the terminal absolute filters. It includes a sealed central passage for the implantation of the operating light.

  • Plenum height possible 300 to 500 mm according to request.

  • Aeraulic connections: circular interlocking or rectangular outlets with frames.

  • Perforated filter protection grids in painted sheet steel or stainless steel.

  • Delivery method :

    Assembled / In two parts

Download the brochure

AIR FLOW DEPENDING ON
THE FILTER OUTPUT SPEED m3/h
SIZE / SPEED 0.25m/s 0.30m/s 0.35m/s
PSOP 16 1300 m3/h 1600 m3/h 1900 m3/h
PSOP 24 2000 m3/h 2400 m3/h 2800 m3/h
PSOP 32 2600 m3/h 3200 m3/h 3800 m3/h
PSOP 44 3600 m3/h 4400 m3/h 5200 m3/h
PSOP 56 4600 m3/h 5600 m3/h 6600 m3/h
PSOP 60 5000 m3/h 6000 m3/h 7000 m3/h
PSOP 76 6300 m3/h 7600 m3/h 8900 m3/h
PSOP 96 8000 m3/h 9600 m3/h 11200 m3/h
DIMENSIONS
Width (mm) Length (mm) Height (mm) Weight (Kg)
PSOP 16 1432 1364 410 100
PSOP 24 2110 1364 410 130
PSOP 32 2110 2042 460 200
PSOP 44 2110 2074 460 250
PSOP 56 3330 2110 460 300
PSOP 60 2788 2720 510 320
PSOP 76 3466 2652 510 400
PSOP 96 3466 3330 510 480